§483.90 Physical Environment.

The facility must be designed, constructed, equipped, and maintained to protect the health and safety of residents, personnel and the public.

§483.90(a) Life safety from fire.

§483.90(a)(1) Except as otherwise provided in this section –

§483.90(a)(1)(i) The LTC facility must meet the applicable provisions and must proceed in accordance with the Life Safety Code (NFPA 101 and Tentative Interim Amendments TIA 12-1, TIA 12-2, TIA 12-3, and TIA 12-4.)

§483.90(a)(1)(ii) Notwithstanding paragraph (a)(1)(i) of this section, corridor doors and doors to rooms containing flammable or combustible materials must be provided with positive latching hardware. Roller latches are prohibited on such doors.

§483.90(a)(2) In consideration of a recommendation by the State survey agency or Accrediting Organization or at the discretion of the Secretary, may waive, for periods deemed appropriate, specific provisions of the Life Safety Code, which would result in unreasonable hardship upon a long-term care facility, but only if the waiver will not adversely affect the health and safety of the patients.

§483.90(a)(3) The provisions of the Life safety Code do not apply in a State where CMS finds, in accordance with applicable provisions of sections 1819(d)(2)(B)(ii) and 1919(d)(2)(B)(ii) of the Act, that a fire and safety code imposed by State law adequately protects patients, residents and personnel in long term care facilities.

§483.90(a)(4) A long-term care facility may install alcohol-based hand rub dispensers in its facility if the dispensers are installed in a manner that adequately protects against inappropriate access.

§483.90(a)(5) A long term care facility must:

§483.90(a)(5)(i) Install, at least, battery-operated single station smoke alarms in accordance with the manufacturer's recommendations in resident sleeping rooms and common areas.

§483.90(a)(5)(ii) Have a program for inspection, testing, maintenance, and battery replacement that conforms to the manufacturer's recommendations and that verifies correct operation of the smoke alarms.

§483.90(a)(5)(iii) Exception:

§483.90(a)(5)(iii)(A) The facility has system-based smoke detectors in patient rooms and common areas that are installed, tested, and maintained in accordance with NFPA 72, National Fire Alarm Code, for system-based smoke detectors; or §483.90(a)(5)(iii)(B) The facility is fully sprinklered in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.

§483.90(a)(6) A long term care facility must:

§483.90(a)(6)(i) Install an approved, supervised automatic sprinkler system in accordance with the 1999 edition of NFPA 13, Standard for the Installation of Sprinkler Systems, as incorporated by reference, throughout the building by August 13, 2013. The Director of the Office of the Federal Register has approved the NFPA 13 1999 edition of the Standard for the Installation of Sprinkler Systems, issued July 22, 1999 for incorporation by reference in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of the Code is available for inspection at the CMS Information Resource Center, 7500 Security Boulevard, Baltimore, MD or at the National Archives and Records Administration (NARA). For information on the availability of this material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations. html. Copies may be obtained from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.

§483.90(a)(6)(ii) Test, inspect, and maintain an approved, supervised automatic sprinkler system in accordance with the 1998 edition of NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, as incorporated by reference. The Director of the Office of the Federal Register has approved the NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 1998 edition, issued January 16, 1998 for incorporation by reference in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of the Code is available for inspection at the CMS Information Resource Center, 7500 Security Boulevard, Baltimore, MD or at the National Archives and Records Administration (NARA). For information on the availability of this material at NARA, call 202-741-6030, or go to: http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations. html. Copies may be obtained from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.

§483.90(a)(6)(iii) Subject to approval by CMS, a long term care facility may be granted an extension of the sprinkler installation deadline for a time period not to exceed 2 years from August 13, 2013, if the facility meets all of the following conditions:

§483.90(a)(6)(iii)(A) It is in the process of replacing its current building, or undergoing major modifications to improve the living conditions for residents in all unsprinklered living areas that requires the movement of corridor, room, partition, or structural walls or supports, in addition to the installation of a sprinkler system; or, has had its planned sprinkler installation so impaired by a disaster or emergency, as indicated by a declaration under section 319 of the Public Health Service Act, that CMS finds it would be impractical to meet the sprinkler installation due date.

§483.90(a)(6)(iii)(B) It demonstrates that it has made the necessary financial commitments to complete the building replacement or modification; or pursuant to a declared disaster or emergency, CMS finds it impractical to make reasonable and necessary financial commitments.

§483.90(a)(6)(iii)(C) Before applying for the deadline extension, it has submitted plans to State and local authorities that are necessary for approval of the replacement building or major modification that includes the required sprinkler installation, and has received approval of the plans from State and local authorities.

§483.90(a)(6)(iii)(D) It agrees to complete interim steps to improve fire safety, as determined by CMS.

§483.90(a)(6)(iv) An extension granted under paragraph (a)(8)(iii) of this section may be renewed once, for an additional period not to exceed 1 year, if the following conditions are met:

§483.90(a)(6)(iv)(A) CMS finds that extenuating circumstances beyond the control of the facility will prevent full compliance with the provisions in paragraph (a)(8)(i) of this section by the end of the first waiver period.

§483.90(a)(6)(iv)(B) All other conditions of paragraph (a)(8)(iii) of this section are met.

§483.90(a)(8) When a sprinkler system is shut down for more than 10 hours, the LTC facility must:

§483.90(a)(8)(i) Evacuate the building or portion of the building affected by the system outage until the system is back in service, or

§483.90(a)(8)(ii) Establish a fire watch until the system is back in service. GUIDANCE: §483.90(a)

For additional guidance on life safety from fire and the survey procedures for these regulatory requirements, reference Appendix I in the SOM. Concerns regarding the above regulatory provisions would be addressed through the Life Safety Code survey (K- Tags).

§483.90(b) Standard: Building safety.

Except as otherwise provided in this section, the LTC facility must meet the applicable provisions and must proceed in accordance with the Health Care Facilities Code (NFPA 99 and Tentative Interim Amendments TIA 12-2, TIA 12-3, TIA 12-4, TIA 12-5 and TIA 12-6).

§483.90(b)(1) Chapters 7, 8, 12, and 13 of the adopted Health Care Facilities Code do not apply to a LTC facility.

§483.90(b)(2) If application of the Health Care Facilities Code required under paragraph (b) of this section would result in unreasonable hardship for the LTC facility, CMS may waive specific provisions of the Health Care Facilities Code, but only if the waiver does not adversely affect the health and safety of residents.

GUIDANCE: §483.90(b)

For additional guidance and procedures on building safety reference Appendix I in the SOM.